As buildings have become tighter, a variety of issues related to roof ventilation—including ice damming, water condensation and mold within the building envelope—have tormented owners and contractors with increasing regularity. Many of these issues have manifested as costly court battles and insurance claims resulting in the general public's heightened awareness of these concerns and increased accountability in the contracting community.
Professional roofing contractors have a distinct role to play to ensure ventilation standards are met—primarily at the ridge.
Ventilation
The ventilation standard is specified in the 2003 International Residential Code (IRC) Sect. R806. For roof areas over heated or conditioned spaces, a net-free ventilation area of 1 square foot per 150 square feet (67 cm²/1 m²) of ceiling area is required. This can be simplified by rounding the equation to 1 square inch of ventilation per square foot of ceiling.
In passive roof ventilation systems, the air flow required is divided evenly between eave vents and ridge vents so convection current naturally pulls cooler air through the soffit vent and exhales warmer air and moisture through the ridge vent. A gable roof forms a triangle with two points of air entry at the soffits and a point of exit at each side of the ridge cap. The net-free air (NFA) rating at each of these points should be roughly equal, and when all four are added, they should equal at least the minimum free air required for the heated space below.
NFA ratings are measured in square inches of free air per foot run of vent (ridge or eave). On a gable roof, the ridge and eaves follow each other parallel to the ridge in the center of the roof and the eaves at either side. If there are no valleys or hips in the roof system, it is relatively easy to determine what the NFA rating needs to be at these locations. You simply divide the width of the building in feet by four to determine the NFA rating required at each point. If a building is 24 feet (7 m) wide, you need an NFA rating of six at each eave vent and on each side of the ridge cap to satisfy the ventilation standard (24 ÷ 4 = 6).
On buildings with cut-up roof lines, this equation still works as long as the total linear footage of soffit is roughly twice the total linear footage of the ridge. When buildings have much more soffit than ridge (as in the case of hipped buildings), an alternative means will be necessary to vent the peak, such as a cupola or mechanical vent. When there is more ridge than soffit (as in the case of multivalleyed roofs), creative means for introducing more air at the eaves needs to be explored.
Intake and exhaust vents must be positioned so they provide continuous air flow. In valleyed and hipped roof systems, it is important to position the intake vents so they feed the roof system evenly and exhaust vents so they draw the air evenly from the intake vents across the deck. When cathedral ceilings are under hipped or valleyed roofs, it often is necessary to design a ventilation system over the roof frame for proper air flow.
The ridge vent system shown in this article is designed for buildings up to 36 feet (11 m) wide with a total NFA rating of 18 (a ridge vent with an NFA rating of 18 has 18 inches [457 mm] NFA per linear foot of ridge vent with an NFA rating of 9 per side). The venting portion of the cap is fabricated from 20-gauge perforated flat sheets with 1/8-inch (3-mm) holes drilled 3/16 of an inch (5 mm) apart. This product has 40 percent of its area open for ventilation. Simple alterations to the measurements of the vent and cap components can increase the NFA rating for wider buildings. We have designed and installed ridge vents for buildings up to 80 feet (24 m) wide with the ridge cap still looking appropriately sized.
We have been using this detail for many years in the conditions we face in the upper peninsula of Michigan. On the shores of Lake Superior, it is not uncommon for winds to approach 50 mph, and inland we can experience 300 inches (7620 mm) of snow during a winter season. We have not experienced snow and water infiltration using this ridge vent detail on our applications.
The use of air baffles at the ridge is particularly important when high-wind conditions are prevalent.
When homeowners experience ongoing problems with ice damming or moisture in an attic, the roofing contractor usually gets the call. Inadequate insulation and ventilation often is the culprit. It is important to be proactive and address these problems before any roof system installations.
Please see the pictures of the details we have developed to address these issues in our area.
Dan Perkins is owner of Dan Perkins Construction Inc., Ishpeming, Mich.
COMMENTS
Be the first to comment. Please log in to leave a comment.