It has long been widely recognized roof membrane blow-off often is caused by inadequate attachment of edge flashings and copings (see Photo 1). A few decades ago, it was common for edge flashings to be attached with cleat clips or to be uncleated. The NRCA Roofing and Waterproofing Manual's 1989 edition and the Sheet Metal & Air Conditioning Contractors' National Association's Architectural Sheet Metal Manual's 1987 edition permitted 4- and 5-inch uncleated vertical faces of edge flashings.
Eventually, it was recognized edge flashings are susceptible to blow-off when they are attached with cleat clips or are uncleated. However, Hurricane Hugo investigations of which I was a part revealed many failures of edge flashings and copings that had continuous cleats. Several of my Hugo recommendations were incorporated into ANSI/SPRI ES-1, "Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems."
Until about a decade ago, it was common for edge flashings and copings to be weaker than the nailers to which they were attached. But with the incorporation of ANSI/SPRI ES-1 into the 2003 edition of the International Building Code (IBC), this has changed. Since the publication of ANSI/SPRI ES-1 in 2003, wind damage investigations have revealed instances where nailers were the weak link in the uplift load path. This is not a new finding (see Photo 2). However, because ANSI/SPRI ES-1 increased attention to edge flashing and coping attachment, nailer failure will become the predominate edge failure mode unless attention also is given to nailer attachment.
ANSI/SPRI ES-1 changes
In 2011, ANSI/SPRI ES-1's title changed to ANSI/SPRI/FM 4435/ ES-1. The 2011 edition is referenced in IBC's 2015 edition (the 2012 IBC references the 2003 edition of ES-1). Nailers were addressed in ANSI/SPRI ES-1's 2003 edition; however, additional information was added to the 2011 edition.
For example, nailer securement load tables were added. Table footnotes include the following notations:
Commentary Section C4.4 notes the nailer securement load tables do not address horizontal loads. If a roof membrane is fully adhered, it is my opinion nailer fasteners typically will have adequate shear resistance. However, if a membrane is mechanically attached and the nailer receives membrane fasteners, the nailer should be designed for the additional load imparted by the membrane (both versions of ANSI/SPRI ES-1 provide guidance for doing so).
In addition, the 2003 and 2011 editions state deteriorated nailers should be replaced. Both editions also state contractors should check existing nailers to ensure they are "well-secured to the building." However, in my opinion, if a designer (architect, engineer or roof consultant) is involved with a reroofing project, the designer should determine whether existing nailers are adequately attached. The 2011 edition gives more stringent criteria than the 2003 edition by requiring fasteners to resist the design wind load rather than the nailers simply being "well-secured."
The Commentary implies the entire load path from the nailers to the foundation should be adequate. For new construction, this is logical. However, for reroofing projects, this can be burdensome. Determining whether an entire load path is adequate can be costly. Additionally, if a load path is inadequate, strengthening it can be expensive. Guidance in the Commentary typically is nonmandatory. Although only the test method portions of ANSI/SPRI ES-1 are referenced by the 2006 and later editions of IBC, the wording in section 3.9.1 of the standard might be incorrectly interpreted by some authorities that have jurisdiction as requiring the Commentary to be mandatory.
With respect to load path, as part of a reroofing project, it is my opinion existing nailers should be attached to their substrate to meet current wind-uplift loads. Depending on a variety of factors (which I would discuss with the building owner), it may not be appropriate to spend the money for other load path improvements.
Common provisions
Both editions of ANSI/SPRI ES-1 have the following nailer provisions of which designers and contractors should be aware:
My recommendations
In addition to the requirements and nonmandatory guidance given in ANSI/SPRI ES-1, I recommend the following:
It is vital nailers be appropriately designed and installed to achieve good wind performance.
Thomas L. Smith, AIA, RRC, F.SEI, is president of TLSmith Consulting Inc., Rockton, Ill.
Know your standards
ANSI/SPRI ES-1 addresses two primary elements of edge system wind design: determining wind loads and determining wind resistance via laboratory testing. For determining wind loads, the 2003 edition is based on the 2002 edition of ASCE 7, "Minimum Design Loads for Buildings and Other Structures." The ANSI/SPRI ES-1's 2011 edition is based on ASCE 7's 2005 edition. With respect to wind loads on roof systems, the 2002 and 2003 editions of ASCE 7 are the same. However, the 2012 and 2015 editions of the International Building Code (IBC) reference ASCE 7's 2010 edition, which is quite different from the previous edition. (For more information about the changes, see "Mapping the 2010 wind changes," August 2010 issue.) IBC references ASCE 7 for determination of wind loads. Therefore, when working with the 2012 or 2015 editions of IBC, make appropriate adjustments when using ANSI/SPRI ES-1.
ANSI/SPRI ES-1 includes test methods for evaluating wind resistance of edge flashings and copings. However, these tests do not typically evaluate nailer resistance. Nailer resistance is evaluated by calculations or by using nailer tables in the 2011 edition of ANSI/SPRI ES-1. The test methods are the only portion of ANSI/SPRI ES-1 that is referenced by the 2006 and later editions of IBC.
COMMENTS
Be the first to comment. Please log in to leave a comment.